Conventional Acoustic Siren CA 65

Characteristics

Properties

Siren is designed for alarming people when fire hazard is detected to let them evacuate. Conventional sirens can be activated by turning on power supply. Device have 32 built-in sound patterns. Sound volume can be adjusted in 3 levels.

 
Technical data  
Power supply voltage 24 [VDC] ± 25%
Max. sound level 99 [dB]
Number of sound patterns 32
Synchronization Yes
Quiescent current consumption 0,2 [mA]
Alarm current consumption 25 [mA]*
Hpusing IP IP21C / IP65**
Working temperature -25 up to 55 [°C]
Admissible relative humidity 95% at temp. 35 [°C]
Dimensions (diameter x height) Ø 119x44 [mm]
Weight 200 [g]
Housing colour Red
Product code FSS332
* current consumption at max volume level
**out of scope of EN54-3

Dimensions

Files to download

CE Declaration

pdf 0.15 MB

CE Certificate

pdf 0.49 MB

Assembly instruction

pdf 2.02 MB

Datasheet

pdf 1.03 MB